InfiniBand optics & cables
InfiniBand uses the same pluggable housings as high-speed Ethernet, but the choice of cable versus transceiver — and the tolerance for third-party modules — follows its own rules shaped by HPC and AI clusters.
Cable or transceiver, by generation
| Generation | Port | Copper DAC | Active optical cable | Transceiver + fibre |
|---|---|---|---|---|
| EDR 100G | QSFP28 | up to ~3–5 m | up to 100 m | SR4 (MPO-12 MMF), LR4 |
| HDR 200G | QSFP56 | up to ~2 m | up to 100 m | SR4/DR4 |
| NDR 400G | OSFP (twin-port 2×400G) | ~1–2 m | limited | DR4/DR8 on MPO-12 APC single-mode |
The pattern: as rates rise, passive copper reach collapses and fabrics move to optics. At NDR the norm is single-mode DR optics with MPO-12 APC connectors — the angled polish is mandatory, and mixing APC with flat UPC connectors is a common installation fault.
Twin-port OSFP
NDR switch ports are commonly twin-port OSFP: one OSFP module carries two independent 400G links (2×DR4), doubling faceplate density. A finned integrated heat sink handles the power. See OSFP.
Signalling and FEC
- EDR: NRZ 25G lanes; HDR: PAM4 50G; NDR: PAM4 100G.
- RS-FEC is mandatory from HDR onward. FEC mismatch or a module that does not advertise the expected FEC is a frequent "link never trains" cause.
Vendor policy
InfiniBand fabrics are dominated by a single switch/NIC vendor, and that vendor's platforms validate cables and optics by identity. A module that is not recognised may read correctly yet fail to link with a status such as "speed and type: Not supported" — see Vendor lock. Operators therefore stock qualified optics and, where third-party modules are used, code them to the expected identity.
Operating at scale
- Thousands of optics per cluster: even a small annual failure rate means a steady stream of replacements. Track per-lane DDM to catch a dying lane before it slows a collective operation.
- Cleanliness on MPO end-faces is the dominant cause of flaps — see CMIS issues for 400G specifics.
In CodingBox
CodingBox reads EDR/HDR modules per SFF-8636 and NDR OSFP/QSFP-DD per CMIS: identity, module state, per-lane DDM, and the identity fields that determine whether a fabric will accept the module.