SFF-8636 registrlar xaritasi: yuqori sahifalar (00h, 03h)
Upper memory (bytes 128–255) of a QSFP+/QSFP28 module is paged through lower byte 127. Page 00h carries the identity block that hosts validate; page 03h carries the alarm/warning thresholds and per-lane signal-integrity controls; pages 01h and 02h hold the application-select table and user EEPROM. This page lists them byte by byte and bit by bit, compiled against SFF-8636 Rev 2.11 (rev 2.10 marks later additions). Narrative: SFF-8636; runtime bytes are in the Lower page 00h map.
Legend: rsvd = reserved · vendor = vendor specific · bit 7 = MSB.
Upper page 00h — identity, bytes 128–191 (covered by CC_BASE)
| Byte | Field | Contents |
|---|---|---|
| 128 | Identifier | as lower byte 0 (0Dh QSFP+, 11h QSFP28) |
| 129 | Extended identifier | 7–6 power class 1–4: 00 class 1 ≤ 1.5 W · 01 class 2 ≤ 2.0 W · 10 class 3 ≤ 2.5 W · 11 class 4 ≤ 3.5 W · 5 power class 8 implemented rev 2.10 (max power in lower byte 107) · 4 CLEI code present (page 02h) · 3 CDR present in Tx · 2 CDR present in Rx · 1–0 power class 5–7: 00 not used (see 7–6) · 01 class 5 ≤ 4.0 W · 10 class 6 ≤ 4.5 W · 11 class 7 ≤ 5.0 W |
| 130 | Connector | SFF-8024 Table 4-3: 07h LC · 0Ch MPO 1×12 · 0Dh MPO 2×16 · 23h no separable connector · 27h MPO 2×12 · 28h MPO 1×16 |
| 131 | Ethernet compliance | 7 extended — use byte 192 · 6 10GBASE-LRM · 5 10GBASE-LR · 4 10GBASE-SR · 3 40GBASE-CR4 · 2 40GBASE-SR4 · 1 40GBASE-LR4 · 0 40G active cable (XLPPI) |
| 132 | SONET compliance | 7–4 rsvd · 3 40G OTN (OTU3B/OTU3C) · 2 OC-48 long reach · 1 OC-48 intermediate · 0 OC-48 short reach |
| 133 | SAS/SATA compliance | 7 SAS 24 Gb/s rev 2.10 · 6 SAS 12 Gb/s · 5 SAS 6 Gb/s · 4 SAS 3 Gb/s · 3–0 rsvd |
| 134 | Gigabit Ethernet compliance | 7–4 rsvd · 3 1000BASE-T · 2 1000BASE-CX · 1 1000BASE-LX · 0 1000BASE-SX |
| 135 | FC link length / technology | 7 very long (V) · 6 short (S) · 5 intermediate (I) · 4 long (L) · 3 medium (M) · 2 rsvd · 1 longwave laser (LC) · 0 electrical inter-enclosure (EL) |
| 136 | FC transmitter technology | 7 electrical intra-enclosure · 6 shortwave laser w/o OFC (SN) · 5 shortwave laser with OFC (SL) · 4 longwave laser (LL) · 3–0 rsvd |
| 137 | FC transmission media | 7 twin axial (TW) · 6 shielded twisted pair (TP) · 5 miniature coax (MI) · 4 video coax (TV) · 3 multimode 62.5 µm (M6) · 2 multimode 50 µm (M5) · 1 OM3 · 0 single mode (SM) |
| 138 | FC speed | 7 1200 MB/s · 6 800 · 5 1600 · 4 400 · 3 3200 · 2 200 · 1 extended (SFF-8024) · 0 100 MB/s |
| 139 | Encoding | SFF-8024 Table 4-2 (QSFP column): 00h unspecified · 01h 8B/10B · 02h 4B/5B · 03h NRZ · 04h SONET scrambled · 05h 64B/66B · 06h Manchester · 07h 256B/257B · 08h PAM4 |
| 140 | Nominal signalling rate | per lane, units of 100 Mb/s (67h = 10.3 Gb/s); FFh → see byte 222 |
| 141 | Extended rate select compliance | 7–2 rsvd · 1–0 01 = rate select version 1 (bytes 87–88 valid); 00 = not implemented |
| 142 | Length SMF | km (00h = not SMF) |
| 143 | Length OM3 | units of 2 m |
| 144 | Length OM2 | units of 1 m |
| 145 | Length OM1 | units of 1 m |
| 146 | Length copper / OM4 | copper or active cable: metres; OM4: units of 2 m (interpretation per byte 147 technology) |
| 147 | Device technology | 7–4 transmitter technology: 0h 850 nm VCSEL · 1h 1310 nm VCSEL · 2h 1550 nm VCSEL · 3h 1310 nm FP · 4h 1310 nm DFB · 5h 1550 nm DFB · 6h 1310 nm EML · 7h 1550 nm EML · 8h other/undefined · 9h 1490 nm DFB · Ah copper unequalised · Bh copper passive equalised · Ch copper near & far end limiting active · Dh copper far end limiting · Eh copper near end limiting · Fh copper linear active equalisers · 3 wavelength control (1 = active) · 2 cooled transmitter · 1 detector type (1 = APD, 0 = PIN) · 0 tunable transmitter |
| 148–163 | Vendor name | 16 ASCII |
| 164 | Extended module | InfiniBand: 7–5 rsvd · 4 EDR · 3 FDR · 2 QDR · 1 DDR · 0 SDR |
| 165–167 | Vendor OUI | — |
| 168–183 | Vendor PN | 16 ASCII |
| 184–185 | Vendor rev | 2 ASCII |
| 186–187 | Wavelength / copper attenuation | optical: wavelength in 0.05 nm units (0x6598 = 1299.2 nm) · copper: 186 attenuation at 2.5 GHz (dB), 187 at 5.0 GHz |
| 188–189 | Wavelength tolerance / attenuation | optical: ±tolerance in 0.005 nm units · copper: 188 at 7.0 GHz, 189 at 12.9 GHz |
| 190 | Max case temperature | °C (00h = 70 °C standard) |
| 191 | CC_BASE | (Σ bytes 128–190) mod 256 |
Upper page 00h — extended identity, bytes 192–255
| Byte | Field | Contents |
|---|---|---|
| 192 | Extended specification compliance | SFF-8024 Table 4-4 (02h 100GBASE-SR4 · 03h LR4 · 06h CWDM4 · 07h PSM4 · 0Bh 100GBASE-CR4 · 11h 4×10GBASE-SR · 25h 100GBASE-DR · 40h–49h 50G/200G/400G codes …) — SFF-8024 |
| 193 | Options | 7 rsvd · 6 LPMode/TxDis pin function configurable rev 2.10 · 5 IntL/LOSL pin function configurable rev 2.10 · 4 Tx input EQ auto-adaptive capable · 3 Tx input EQ fixed programmable · 2 Rx output emphasis fixed programmable · 1 Rx output amplitude fixed programmable · 0 rsvd |
| 194 | Options | 7 Tx CDR on/off control implemented · 6 Rx CDR on/off control implemented · 5 Tx CDR LOL flag implemented · 4 Rx CDR LOL flag implemented · 3 Rx squelch disable implemented · 2 Rx output disable capable · 1 Tx squelch disable implemented · 0 Tx squelch implemented |
| 195 | Options | 7 page 02h provided · 6 page 01h provided · 5 rate select implemented · 4 Tx_Disable implemented · 3 Tx_Fault implemented · 2 Tx squelch reduces OMA (1) or Pave (0) · 1 Tx LOS implemented · 0 pages 20h–21h implemented |
| 196–211 | Vendor SN | 16 ASCII |
| 212–219 | Date code | YYMMDD + 2 lot |
| 220 | Diagnostic monitoring type | 7–4 rsvd · 3 Rx power measurement: 1 = average, 0 = OMA · 2 Tx power monitor implemented · 1–0 rsvd |
| 221 | Enhanced options | 4 initialisation-complete flag implemented (lower byte 6 bit 0) · 3 rate selection declaration (0 = via byte 141 / rate select v1, 1 = via application select page 01h) · 2–0 later-revision features (TC readiness flag, software reset, Tx-disable fast mode) — check the revision |
| 222 | Extended signalling rate | per lane, units of 250 Mb/s, valid when byte 140 = FFh (67h = 25.75 Gb/s; D5h = 53.125 GBd) |
| 223 | CC_EXT | (Σ bytes 192–222) mod 256 |
| 224–255 | Vendor specific | not checksummed; signatures and production data |
Page 01h — application select table
Populated only when byte 195 bit 6 is set; defines applications selectable through lower bytes 89–92 / 94–97 (SFF-8079 model). Rarely implemented on QSFP28; CMIS replaced it with application descriptors.
Page 02h — user EEPROM
| Bytes | Contents |
|---|---|
| 128–137 | CLEI code (10 ASCII) when byte 129 bit 4 is set |
| 128–255 | otherwise free user EEPROM, not checksummed |
Page 03h — thresholds, bytes 128–223
| Bytes | Field | Bytes | Field |
|---|---|---|---|
| 128–129 | Temperature high alarm | 130–131 | Temperature low alarm |
| 132–133 | Temperature high warning | 134–135 | Temperature low warning |
| 136–143 | rsvd | — | — |
| 144–145 | Vcc high alarm | 146–147 | Vcc low alarm |
| 148–149 | Vcc high warning | 150–151 | Vcc low warning |
| 152–175 | rsvd / vendor | — | — |
| 176–177 | Rx power high alarm | 178–179 | Rx power low alarm |
| 180–181 | Rx power high warning | 182–183 | Rx power low warning |
| 184–185 | Tx bias high alarm | 186–187 | Tx bias low alarm |
| 188–189 | Tx bias high warning | 190–191 | Tx bias low warning |
| 192–193 | Tx power high alarm | 194–195 | Tx power low alarm |
| 196–197 | Tx power high warning | 198–199 | Tx power low warning |
| 200–223 | rsvd | — | — |
Channel thresholds apply to all four lanes; formats as the monitors (temperature 1/256 °C, Vcc 100 µV, bias 2 µA, power 0.1 µW) — Thresholds & alarms.
Page 03h — channel controls and masks, bytes 224–255
| Byte | Field | Bits |
|---|---|---|
| 224–225 | vendor | — |
| 226–233 | rsvd / vendor | — |
| 234 | Tx input equalisation | 7–4 Tx1 EQ level · 3–0 Tx2 EQ level (0–15, dB steps per vendor) |
| 235 | Tx input equalisation | 7–4 Tx3 · 3–0 Tx4 |
| 236 | Rx output emphasis | 7–4 Rx1 · 3–0 Rx2 |
| 237 | Rx output emphasis | 7–4 Rx3 · 3–0 Rx4 |
| 238 | Rx output amplitude | 7–4 Rx1 · 3–0 Rx2 (codes 0–3: 100–400 / 300–600 / 400–800 / 600–1200 mVpp) |
| 239 | Rx output amplitude | 7–4 Rx3 · 3–0 Rx4 |
| 240 | Squelch disable | 7–4 Rx4…Rx1 squelch disable · 3–0 Tx4…Tx1 squelch disable |
| 241 | Rx output disable | 7–4 rsvd · 3–0 Rx4…Rx1 output disable |
| 242 | Rx power masks lanes 1–2 | layout as lower byte 9 |
| 243 | Rx power masks lanes 3–4 | as lower byte 10 |
| 244 | Tx bias masks lanes 1–2 | as lower byte 11 |
| 245 | Tx bias masks lanes 3–4 | as lower byte 12 |
| 246 | Tx power masks lanes 1–2 | as lower byte 13 |
| 247 | Tx power masks lanes 3–4 | as lower byte 14 |
| 248–253 | rsvd | — |
| 254–255 | vendor | — |
Pages 20h–21h
Optional (byte 195 bit 0); rev 2.10 reserves them for extended per-lane functions and vendor use — consult the module's datasheet.
Reading a 100GBASE-SR4 identity
A typical SR4 reads: byte 128 = 11h; 129 = 00h (class 1) or 40h (class 2); 130 = 0Ch (MPO); 131 = 80h (extended); 139 = 05h (64B/66B); 140 = FFh; 222 = 67h (25.75 Gb/s per lane); 143 = 23h (70 m OM3 in 2 m units = 35); 146 = 32h (100 m OM4 / 2 = 50); 147 = 00h (850 nm VCSEL, PIN); 186–187 = 850 nm / 0.05 = 17 000 = 4268h (the exact value depends on the module's nominal wavelength field); 192 = 02h (100GBASE-SR4); 195 = 3Ch–BCh depending on the pages provided. Values differ between vendors; the point is which bytes to look at.
Related maps
- Lower page 00h map — flags, monitors, controls.
- SFF-8472 A0h map — the SFP equivalent of the identity block.
- CMIS upper pages map — the CMIS equivalent.