CodingBox Nyaraka

Bendi za urefu wa wimbi na mipango ya chaneli

Every optical module lives at a wavelength, and every wavelength belongs to a named band with its own fibre loss, amplifier availability and typical uses. This page is the lookup table: bands, the wavelengths you will meet on module labels, and the WDM grids.

The named bands (single-mode)

BandRangeNameLoss (G.652.D)Typical use
O1260–1360 nmOriginal~0.33–0.35 dB/km1310 nm LR/DR/FR optics, PON upstream, LAN-WDM, CWDM 1271–1351
E1360–1460 nmExtended0.3–0.5 dB/km, water peak ~1383 nmCWDM 1371–1451 on low-water-peak fibre only
S1460–1530 nmShort~0.25 dB/kmCWDM 1471–1511, GPON downstream 1490, OSC 1510
C1530–1565 nmConventional~0.18–0.22 dB/km (minimum)DWDM, EDFA band, 1550 nm ER/ZR, CWDM 1531/1551
L1565–1625 nmLong~0.2–0.25 dB/kmL-band DWDM, XGS-PON downstream 1577, CWDM 1571–1611, NG-PON2
U1625–1675 nmUltra-longrisingmonitoring / OTDR test wavelengths (1625, 1650)

Multi-mode fibre uses 850 nm (VCSEL) and, on legacy links, 1300 nm; its loss is ~3 dB/km, so reach is set by bandwidth rather than attenuation (Connectors & fibre).

Wavelengths you meet on labels

WavelengthWhere
850 nmSX, SR, SR4, SR8, AOC — multi-mode
1270 / 1330 nm10G BiDi pair; XGS-PON upstream (1270)
1310 nmLX, LR, DR, PSM4, FR — the single-mode workhorse
1295–1310 nm (4 λ)LAN-WDM: 100GBASE-LR4/ER4, 400GBASE-FR8/LR8
1271–1331 nm (4 λ)CWDM4, 40GBASE-LR4, 400GBASE-FR4/LR4
1490 nmGPON downstream; 1G BiDi pair with 1310
1510 nmoptical supervisory channel in DWDM systems
1550 nmEX/ZX, ER, ZR; RF video overlay in PON
1577 nmXG-PON / XGS-PON / 10G-EPON downstream
1528–1565 nmDWDM C-band channels
1596–1603 / 1524–1544 nmNG-PON2 TWDM downstream / upstream

BiDi pairs

Single-fibre bi-directional modules use two wavelengths; the two ends must be the mirror pair (often labelled -U/-D or -A/-B):

PairRateStandard
1310 / 14901G1000BASE-BX10
1310 / 15501G1000BASE-BX (long)
1270 / 133010G10GBASE-BX
1270 / 133025G25G BiDi
1490 / 15501G/10Gvendor pairs

PON wavelength plans (GPON, XGS-PON, NG-PON2, coexistence) are detailed in PON wavelength plans & coexistence.

CWDM grid (ITU-T G.694.2)

18 channels, 20 nm apart. Centre wavelengths in nm:

1271  1291  1311  1331  1351  1371  1391  1411  1431
1451  1471  1491  1511  1531  1551  1571  1591  1611

Common 8-channel systems use 1471–1611 nm; 16-channel systems add 1311–1451 on low-water-peak fibre. Colour codes, muxes and budget: CWDM channel plan, CWDM mux/demux & link budget.

DWDM grid (ITU-T G.694.1)

Defined in frequency, anchored at 193.1 THz. On the 100 GHz grid a channel number N maps to frequency as:

f (THz)  = 190 + N / 10          e.g. C31 → 193.1 THz → 1552.52 nm
N        = (f − 190) × 10
λ (nm)   = 299 792.458 / f (THz)
ChannelFrequencyWavelength
C17191.7 THz1563.86 nm
C21192.1 THz1560.61 nm
C31193.1 THz1552.52 nm
C41194.1 THz1544.53 nm
C51195.1 THz1536.61 nm
C61196.1 THz1528.77 nm

The 50 GHz grid interleaves half-channels (e.g. C31.5 = 193.15 THz). Channel labels vary by vendor — always confirm by frequency. Full treatment: DWDM and the ITU grid.

Amplification windows

AmplifierBandNote
EDFA (C)~1530–1565 nmstandard DWDM amplifier
EDFA (L)~1570–1610 nmdoubles fibre capacity
Ramanany, pump-defineddistributed, extends spans
SOAO-band and othersin-module pre-amplification

CWDM channels outside the C/L bands cannot use EDFAs — the root of CWDM's reach limit.

Where the wavelength lives in memory

A module reports its nominal wavelength in the identity block — SFF-8472 A0h bytes 60–61 (nm), SFF-8636 upper page 00h bytes 186–187 (÷20 nm) — and tunable modules expose channel/frequency registers (Tunable memory maps). CodingBox shows it on the Check transceiver screen; when recoding, keep it equal to the laser's real wavelength.

How wavelengths are printed on labels and encoded in latch colours (CWDM channel colours, BiDi pairs): Labels & colour codes; the ITU-T recommendations behind the grids: Standards map.

Why these windows exist — Rayleigh scattering, absorption, the water peak — and attenuation per fibre type and wavelength: Attenuation and transmission windows.